MCC Panels

HMI & SCADA Systems in Custom Engineered Panel

HMI & SCADA Systems selection, integration, and best practices for Custom Engineered Panel assemblies compliant with IEC 61439.

HMI & SCADA Systems in Custom Engineered Panel

Overview

HMI & SCADA Systems in a Custom Engineered Panel are no longer limited to simple operator touchscreens; they are central to plant visibility, control, diagnostics, and lifecycle data management. In IEC 61439-2 assemblies, the HMI architecture must be treated as part of the complete low-voltage switchgear and controlgear assembly, with attention to temperature rise, creepage and clearance, segregation, EMC, and service accessibility. Typical implementations combine a front-door HMI, industrial PC, managed Ethernet switch, protocol gateway, UPS, remote I/O, and SCADA interface modules, all coordinated with the panel’s distribution equipment such as ACBs, MCCBs, contactors, overload relays, soft starters, and VFDs. For engineered panels feeding process lines, water treatment plants, HVAC plants, or utility substations, the HMI is often used to visualize motor status, protective relay alarms, feeder load trends, and energy meters tied into Modbus RTU/TCP, Profinet, Ethernet/IP, or BACnet networks. Selection must start with the enclosure environment and duty. Panel builders should verify the HMI’s operating temperature range, vibration resistance, ingress protection, and front-of-door sealing to match the assembly design, especially when the enclosure is mounted in dusty, humid, or washdown areas. In many applications, a 24 VDC industrial HMI with isolated communication ports is preferred, supported by a control power supply and, where required, a DC UPS to maintain alarm logging and orderly shutdown. For higher availability, redundant switches and mirrored SCADA nodes may be used. If the panel is installed in hazardous areas or near classified zones, related equipment selection must consider IEC 60079 requirements, and if arc-flash energy containment is a design objective, the enclosure and internal arrangement should also be evaluated against IEC/TR 61641 where applicable. From a coordination perspective, the HMI and SCADA hardware must not compromise the assembly’s short-circuit rating or thermal performance. The final panel rating may be 400 A, 800 A, 1600 A, 2500 A, or higher, with a declared short-circuit withstand such as 25 kA, 36 kA, 50 kA, or 70 kA depending on the upstream protective device and internal busbar design. Although the HMI itself carries negligible load current, its power supply, network switches, relays, and auxiliary protection devices must be integrated so they do not exceed permissible losses or invalidate the verified design under IEC 61439-1 and IEC 61439-2. In multi-compartment panels, forms of separation such as Form 2, Form 3b, or Form 4 can be applied to isolate the automation section from power feeders, improving service continuity and reducing disturbance during maintenance. For process industries and building automation, the most common configurations include a 7-inch to 15-inch panel-mount HMI, one or more PLCs, digital/analog I/O, and SCADA connectivity through secure Ethernet architecture. Energy monitoring via multifunction meters, protection relays with IEC 60255 functions, and status feedback from MCC feeders allows centralized diagnostics and predictive maintenance. A properly engineered Custom Engineered Panel will align the HMI & SCADA layout with cable routing, cooling strategy, and door cutout reinforcement so that the assembly remains compliant, maintainable, and scalable for future expansion. Patrion, based in Turkey, supports such panels with engineering, manufacturing, and integration expertise for demanding industrial applications.

Key Features

  • HMI & SCADA Systems rated for Custom Engineered Panel operating conditions
  • IEC 61439 compliant integration and coordination
  • Thermal management within panel enclosure limits
  • Communication-ready for SCADA/BMS integration
  • Coordination with upstream and downstream protection devices

Specifications

PropertyValue
Panel TypeCustom Engineered Panel
ComponentHMI & SCADA Systems
StandardIEC 61439-2
IntegrationType-tested coordination

Other Components for Custom Engineered Panel

Other Panels Using HMI & SCADA Systems

Frequently Asked Questions

A typical architecture includes a panel-mount HMI, industrial PLC or PAC, managed Ethernet switch, protocol gateway, 24 VDC power supply, and often a DC UPS for data retention and controlled shutdown. In larger assemblies, remote I/O, energy meters, and protection relays are integrated to provide feeder visibility and alarm management. For IEC 61439-2 compliance, the hardware must be arranged so that heat dissipation, accessibility, and wiring segregation are maintained without compromising the assembly’s verified design. Common communications include Modbus TCP, Modbus RTU, Profinet, Ethernet/IP, and BACnet depending on the plant standard.
HMI sizing is not based on current load, but its thermal contribution still matters because the enclosure has a defined temperature-rise limit under IEC 61439-1/2. Engineers should account for the heat generated by the HMI, PLC, switches, power supplies, and any industrial PC, then verify the overall internal loss budget against the enclosure ventilation or air-conditioning design. In hot environments, derating, filtered fans, thermostatic cooling, or panel air conditioners may be required. The HMI should be specified for the ambient temperature, typically 0 to 50 °C or higher for industrial-grade units, and mounted with sufficient clearance from heat-producing devices like VFDs or soft starters.
Yes, indirectly. The HMI itself is a low-power device, but its associated wiring, power supplies, network components, and auxiliary terminals must be protected so they can withstand the declared assembly short-circuit rating. Under IEC 61439, the panel builder must ensure the complete internal circuit arrangement remains safe at the specified prospective short-circuit current, such as 25 kA, 36 kA, 50 kA, or 70 kA, depending on the design. This is usually achieved by correct upstream protection with MCCBs or fuses, proper separation, and verification of component withstand ratings. The HMI section should be isolated from power circuits where practical.
The most common protocols are Modbus TCP, Modbus RTU, Profinet, Ethernet/IP, and BACnet, with OPC UA increasingly used for secure data exchange with higher-level SCADA and MES systems. The choice depends on the plant automation standard, PLC vendor, and BMS or utility interface requirements. In a Custom Engineered Panel, the communication layer should be designed with managed switches, shielded cabling, proper grounding, and network segmentation to reduce noise and cyber risk. For demanding applications, remote access should be controlled through industrial firewalls or secure gateways rather than direct open connections.
The primary assembly standard is IEC 61439-1 and IEC 61439-2 for low-voltage switchgear and controlgear assemblies. Individual device standards also apply: IEC 60947 for switchgear and controlgear components such as MCCBs, contactors, and auxiliaries; IEC 60255 for protection relays; IEC 61131 for PLC-related control functions; and IEC 60529 for ingress protection. If the installation is in a hazardous area, IEC 60079 requirements become relevant. For arc fault containment or verification considerations, IEC/TR 61641 may also be referenced depending on the project specification.
For many engineered panels, Form 2 or Form 3b separation is a practical choice, while Form 4 is used when higher operational continuity or maintenance isolation is required. The goal is to keep the HMI, PLC, and communication equipment separated from power feeders such as ACBs, MCCBs, VFDs, and soft starters. This improves serviceability and limits the impact of faults or heat from power circuits on the automation layer. The final choice depends on the maintenance philosophy, cable entry design, and the verified IEC 61439 arrangement.
VFDs and soft starters are typically integrated through hardwired signals and digital communications so the HMI can display status, faults, speed reference, current, and trip history. In a Custom Engineered Panel, these drives are often grouped in MCC sections with line reactors, EMC filters, and dedicated cooling because they add significant thermal load. The SCADA layer can read alarms and trends from each drive while the protection device upstream ensures proper coordination. This arrangement must be validated under IEC 61439 so the thermal rise, busbar loading, and component withstand remain within the declared panel ratings.
Reliability comes from using industrial-grade hardware, proper thermal management, and robust power and network design. A 24 VDC redundant or buffered supply, a small DC UPS, and managed Ethernet switches greatly improve uptime. The HMI should be selected with an industrial temperature rating, front IP protection, and spare memory margin for future graphics and alarms. In critical facilities such as water plants, hospitals, or process lines, the SCADA architecture should also include alarm logging, event timestamps, and backup communication paths. Good panel layout under IEC 61439 reduces failures caused by heat, vibration, or wiring errors.

Ready to Engineer Your Next Panel?

Our team of electrical engineers is ready to design, build, and deliver your custom panel solution — fully compliant with international standards.